Description

U Protect WM 4.0 is part of ISOVER solutions for providing fire resistance in HVAC applications by using high performing ULTIMATE mineral wool.

U Protect wired mats provide fire resistant, an easy to install, lightweight and efficient thermal and acoustic insulation solution in HVAC for circular and rectangular ventilation and smoke extraction ducts up to EI 120.

Installation guidelines must be followed and all ISOVER U Protect components used.

Key Benefits

  • Sound absorption
  • Fire resistance
  • Reduced carbon footprint
  • Fast installation

Technical Characteristics

Symbol Unit Quantities and declared values Standard
Reaction to fire Symbol- Unit- Quantities and declared valuesNon-combustible, Euroclass A1 StandardEN 13501-1
Water behaviour Quantities and declared valuesHydrophobic StandardEN 12086
Chemical behaviour Quantities and declared valuesSilicone-free, Sulphide-free StandardAGI Q 132
Application field Quantities and declared valuesU Protect Wired Mats offer fire-resistant insulation for HVAC systems. It’s lightweight, easy to install, and provide efficient thermo-acoustic insulation for circular and rectangular ducts up to EI 120. StandardEN 1366-1 EN 1366-8
CE marking Quantities and declared valuesMW-EN14303-T2-ST(+)400-MV2 StandardEN 14303
Instructions for use Quantities and declared valuesInstallation guidelines must be followed and Protect BSF and BSK must be used to achieve the performance. Standard-
Quality management Quantities and declared valuesISOVER is certified according to EN ISO 9001 and EN ISO 14001 StandardEN ISO 9001 EN ISO 14001

Thermal Conductivity

Characteristic Symbol Unit Quantities and declared values Standard
CharacteristicThermal conductivity SymbolT Unit[°C] Quantities and declared values10 Quantities and declared values_50 Quantities and declared values__100 Quantities and declared values___150 Quantities and declared values____200 Quantities and declared values_____300 Quantities and declared values______400 Quantities and declared values_______500 Quantities and declared values________600 StandardEN 12667
CharacteristicThermal behaviour Symbolλ Unit[W/(m•K)] Quantities and declared values0.033 Quantities and declared values_0.037 Quantities and declared values__0.043 Quantities and declared values___0.049 Quantities and declared values____0.057 Quantities and declared values_____0.073 Quantities and declared values______0.093 Quantities and declared values_______0,117 Quantities and declared values________0,146
CharacteristicThermal conductivity SymbolT Unit[°C] Quantities and declared values< 400 °C (tape and alu-facing 80 °C) StandardEN 14706
CharacteristicMelting point Quantities and declared values> 1,000 ºC Standard-

Acoustic Parameters

Characteristic Symbol Unit Quantities and declared values Thickness [mm] Standard
CharacteristicAcoustics Symbolαw Unit- Quantities and declared valuesWeighted sound absorption coefficient = 0.90 Thickness [mm]- StandardEN 11654
CharacteristicAcoustics Symbol- UnitkPa·S/m3 Quantities and declared valuesSpecific airflow resistance Afr = 60 (measured without facing) Thickness [mm]- StandardEN 29053

Standard Dimensions

Thickness d [mm] Width b [mm] Length [mm] m2/pallet m2/pack
Thickness d [mm]30 Width b [mm]600 Length [mm]10,000 m2/pallet216 m2/pack12.00
Thickness d [mm]40 Width b [mm]600 Length [mm]7,500 m2/pallet162 m2/pack9.00
Thickness d [mm]50 Width b [mm]600 Length [mm]6,000 m2/pallet129.6 m2/pack7.20
Thickness d [mm]60 Width b [mm]600 Length [mm]5,000 m2/pallet108 m2/pack6.00
Thickness d [mm]70 Width b [mm]600 Length [mm]4,300 m2/pallet92.9 m2/pack5.16
Thickness d [mm]75 Width b [mm]600 Length [mm]4,000 m2/pallet86.4 m2/pack4.80
Thickness d [mm]80 Width b [mm]600 Length [mm]3,700 m2/pallet79.9 m2/pack4.44
Thickness d [mm]90 Width b [mm]600 Length [mm]3,300 m2/pallet71.28 m2/pack3.96
Thickness d [mm]100 Width b [mm]600 Length [mm]3,000 m2/pallet64.8 m2/pack3.60
Thickness d [mm]120 Width b [mm]600 Length [mm]2,500 m2/pallet54 m2/pack3.00
Notes
* Check availability and delivery details from your local Isover supplier. 125 mm must be installed in 2 layers 75 mm + 50 mm. U Protect Wired Mats are always loaded with 1000 Pa (i.e. approx. 100 kg/m2) when the thickness is determined, which means that the prescribed thickness is maintained.

Documents

U Protect Wired Mat 4.0 Alu1
TDS_U_Protect_Wired_Mat_4.0_Alu1.pdf
U Protect Wired Mat 4.0 Alu1
HVAC Fire Protection Brochure
U Protect Wired Mat 4.0 Alu1
Insulation Solutions for HVAC Applications
U Protect Wired Mat 4.0 Alu1
ISOVER_Brochure_ULTIMATE-Light-stone-wool
U Protect Wired Mat 4.0 Alu1
SGTI_Brochure_HVAC_Saint-Gobain-Technical-Insulation.pdf
U Protect Wired Mat 4.0 Alu1
Ultimate Fire Protection 2025.pdf
U Protect Wired Mat 4.0 Alu1
U Protect Installation Manual
U Protect Wired Mat 4.0 Alu1
DOP_ULTIMATE-Protect-EN14303_ISOVER.pdf
U Protect Wired Mat 4.0 Alu1
U_Protect_4.0_ETA.pdf
U Protect Wired Mat 4.0 Alu1
EPD_Ultimate.pdf
U Protect Wired Mat 4.0 Alu1
EUCEB_Certificate_CLIMAVER.pdf
U Protect Wired Mat 4.0 Alu1
M1_3509_Ultimate_and_Stone_Wool_2023-10-10_en
U Protect Wired Mat 4.0 Alu1
SUIS_Ultimate.pdf