Description
U TECH Pipe Section MT 4.0 is the efficient and light alternative for the insulation of industry process pipelines for standard pipe diameters from 15 mm to 356 mm (1/2'' to 14''). The ULTIMATE mineral wool preformed concentric-rolled pipe section is equipped with a pre-slit to facilitate the opening and fitting over the pipes.
U TECH Pipe Section MT 4.0 are light and easy to handle. With a length of 1.2 m, installation time on straight pipes and thermal bridges threw joints can be reduced by 20 %.
U TECH Pipe Section MT 4.0 can be used for service temperatures of up to 660 °C.
U TECH Pipe Section MT 4.0 are light and easy to handle. With a length of 1.2 m, installation time on straight pipes and thermal bridges threw joints can be reduced by 20 %.
U TECH Pipe Section MT 4.0 can be used for service temperatures of up to 660 °C.
Key Benefits
- High service temperatures
- Cost effective solution
- Sound absorption
- Fast installation
- Nuclear plant quality
- Fire reaction
Technical Characteristics
Symbol | Unit | Quantities and declared values | Standard | |
---|---|---|---|---|
Specific thermal capacity | Symbolc | UnitkJ/(kg·K) | Quantities and declared values1.03 | StandardISO 10456 |
Reaction to fire | Symbol- | Unit- | Quantities and declared valuesNon combustible; Euroclass A1L Fire Spread Index = 0; Smoke Development Index < 20 IMO-Resolution MSC.61(67); IMO MSC/Circ. 1120 | StandardEN 13501-1 ASTM E84 |
Water behaviour | Quantities and declared values No short term water absorption by partial immersion (WS1 ≤ 1 kg/m2) | Standard- | ||
Chemical behaviour | Quantities and declared valuesAS-quality (Leachable Chloride ≤10ppm) Leachable chloride content less than 10 ppm (CL10) Do not contribute to corrosion of stainless steel Especially designed and certified for use in nuclear applications | StandardAGI Q132 EN 13468 ASTM C795/871 | ||
Application field | Quantities and declared valuesProduct for use in technical applications, such as big diameter pipes, exhaust ducts and stacks, with need for: thermal and/or acoustic insulation with high performances especially at high temperatures. Certified for use in nuclear applications. Especially designed and certified for use in nuclear applications. | StandardEN 14303 | ||
Linear Shrinkage | Unit% | Quantities and declared values<2% (at 700°C) | StandardASTM C356 | |
Material | Unit- | Quantities and declared valuesULTIMATE mineral wool, preformed concentric in shape of pipe section. With quality marks EUCEB and RAL by the Gütegemeinschaft Mineralwolle e. V., unrisky regarding health according to German decree on dangerous substances, decree on prohibition of chemicals and to regulation EC No 1272/2008 Note Q | StandardCINI 2.2.03 | |
Miscellaneous | Quantities and declared valuesInsulating material identification number: 10.04.03.99.99 Designation code : MW-EN14303-T8-ST(+)660-WS1-CL10 (outside pipe ø ≤ 150 mm) Designation code : MW-EN14303-T9-ST(+)660-WS1-CL10 (outside pipe ø > 150 mm) | StandardAGI Q 132 EN14303 | ||
Quality management | Quantities and declared valuesCE-marked according to EN 14303 Quality control according to VDI 2055 ISOVER is certified according to EN ISO 9001 and EN ISO 14001 | StandardEN 14303 EN ISO 9001 EN ISO 14001 |
Thermal Conductivity
Characteristic | Symbol | Unit | Quantities and declared values | Standard | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
CharacteristicThermal conductivity | SymbolT | Unit[°C] | Quantities and declared values40 | Quantities and declared values_50 | Quantities and declared values__100 | Quantities and declared values___150 | Quantities and declared values____200 | Quantities and declared values_____300 | Quantities and declared values______- | StandardASTM C335 ISO 8497 EN ISO 13787 |
||
Symbolλ | Unit[W/(m•K)] | Quantities and declared values0.035 | Quantities and declared values_0.037 | Quantities and declared values__0.043 | Quantities and declared values___0.052 | Quantities and declared values____0.062 | Quantities and declared values_____0.092 | |||||
CharacteristicThermal behaviour | SymbolT | Unit[°C] | Quantities and declared valuesMaximum service temperature 660 (under 500 Pa) Maximum service temperature 700 |
StandardEN 14707 C447/C411 |
Standard Dimensions
Thickness d [mm] |
---|
Thickness d [mm]20 |
Thickness d [mm]30 |
Thickness d [mm]40 |
Thickness d [mm]50 |
Thickness d [mm]60 |
Thickness d [mm]70 |
Thickness d [mm]80 |
Thickness d [mm]90 |
Thickness d [mm]100 |
Thickness d [mm]120 |
Notes
* The information refers to linear meters / pack.
All dimensions require minimum order quantities / other dimensions on request.
All dimensions require minimum order quantities / other dimensions on request.